NiCd sealed batteries are similar in most respects to NiCd vented batteries, but do not normally require the addition of water. Fully discharging the battery (to zero volts) may cause irreversible damage to one or more cells, leading to eventual battery failure due to low capacity. The state of charge of a NiCd battery cannot be determined by measuring the specific gravity of the potassium hydroxide electrolyte. The electrolyte specific gravity does not change with the state of charge. The only accurate way to determine the state of charge of a NiCd battery is by a measured discharge with a NiCd battery charger and following the manufacturer’s instructions. After the battery has been fully charged and allowed to stand for at least 2 hours, the fluid level may be adjusted, if necessary, using distilled or demineralized water. Because the fluid level varies with the state of charge, water should never be added while the battery is installed in the aircraft. Overfilling the battery results in electrolyte spewage during charging. This causes corrosive effects on the cell links, self-discharge of the battery, dilution of the electrolyte density, possible blockage of the cell vents, and eventual cell rupture.
Constant current battery chargers are usually provided for NiCd batteries because the NiCd cell voltage has a negative temperature coefficient. With a constant voltage charging source, a NiCd battery having a shorted cell might overheat due to excessive overcharge and undergo a thermal runaway, destroying the battery and creating a possible safety hazard to the aircraft. Pulsed-current battery chargers are sometimes provided for NiCd batteries. Caution: It is important to use the proper charging procedures for batteries under test and maintenance. These charging regimes for reconditioning and charging cycles are defined by the aircraft manufacturer and should be closely followed.
Aircraft Battery Inspection Aircraft battery inspection consists of the following items: 1. Inspect battery sump jar and lines for condition and security. 2. Inspect battery terminals and quickly disconnect plugs and pins for evidence of corrosion, pitting, arcing, and burns. Clean as required. 3. Inspect battery drain and vent lines for restriction, deterioration, and security. 4. Routine preflight and postflight inspection procedures should include observation for evidence of physical damage, loose connections, and electrolyte loss. Ventilation Systems Modern airplanes are equipped with battery ventilating systems. The ventilating system removes gasses and acid fumes from the battery in order to reduce fire hazards and to eliminate damage to airframe parts. Air is carried from a scoop outside the airplane through a vent tube to the interior of the battery case. After passing over the top of the battery, air, battery gasses, and acid fumes are carried through another tube to the battery sump. This sump is a glass or plastic jar of at least one pint capacity. In the jar is a felt pad about 1 inch thick saturated with a 5-percent solution of bicarbonate of soda and water. The tube carrying fumes to the sump extends into the jar to within about 1⁄4 inch of the felt pad.
An overboard discharge tube leads from the top of the sump jar to a point outside the airplane. The outlet for this tube is designed so there is negative pressure on the tube whenever the airplane is in flight. This helps to ensure a continuous flow of air across the top of the battery through the sump and outside the airplane. The acid fumes going into the sump are neutralized by the action of the soda solution, thus preventing corrosion of the aircraft’s metal skin or damage to a fabric surface. Installation Practices • External surface—Clean the external surface of the battery prior to installation in the aircraft.
• Replacing lead-acid batteries—When replacing lead-acid batteries with NiCd batteries, a battery temperature or current monitoring system must be installed. Neutralize the battery box or compartment and thoroughly flush with water and dry. A flight manual supplement must also be provided for the NiCd battery installation. Acid residue can be detrimental to the proper functioning of a NiCd battery, as alkaline is to a lead-acid battery. • Battery venting—Battery fumes and gases may cause an explosive mixture or contaminated compartments and should be dispersed by adequate ventilation. Venting systems often use ram pressure to flush fresh air through the battery case or enclosure to a safe overboard discharge point. The venting system pressure differential should always be positive and remain between recommended minimum and maximum values. Line runs should not permit battery overflow fluids or condensation to be trapped and prevent free airflow.
• Battery sump jars—A battery sump jar installation may be incorporated in the venting system to dispose of battery electrolyte overflow. The sump jar should be of adequate design and the proper neutralizing agent used. The sump jar must be located only on the 9-25 Failure of one or more cells to rise to the required 1.55 volts at the end of charge Negative electrode not fully charged Cellophane separator damage Discharge battery and recharge. If the cell still fails to rise to 1.55 volts or if the cell’s voltage rises to 1.55 volts or above and then drops, remove cell and replace. Distortion of cell case to cover Overcharged, overdischarged, or overheated cell with internal short Plugged vent cap Overheated battery Discharge battery and disassemble.
Replace defective cell. Recondition battery. Replace vent cap. Check voltage regulator: treat battery as above, replacing battery case and cover and all other defective parts. Frequent addition of water Cell out of balance Damaged “O” ring, vent cap Leaking cell Charge voltage too high Recondition battery. Replace damaged parts. Discharge battery and disassemble. Replace defective cell, recondition battery. Adjust voltage regulator. Corrosion of top hardware Acid flumes or spray or other corrosive atmosphere Replace parts. Battery should be kept clean and kept away from such environments. Distortion of battery case and/or cover. Explosion caused by: Dry cells Charger failure High charge voltage Plugged vent caps Loose intercell connectors Discharge battery and disassemble.
Replace damaged parts and recondition. Discolored or burned end connectors or intercell connectors. Dirty connections. Loose connection. Improper mating of parts. Clean parts: replace if necessary. Retighten hardware using proper torque values. Check to see that parts are properly mated. Foreign material within the cell case Introduced into cell through addition of impure water or water contaminated with acid Discharge battery and disassemble, remove cell and replace, recondition battery. Trouble Probable Cause Corrective Action Apparent loss of capacity Very common when recharging on a constant potential bus, as in aircraft Usually indicates imbalance between cells because of difference in temperature, charge efficiency, self-discharge rate, etc., in the cells Electrolyte level too low Battery not fully charged Reconditioning will alleviate this condition.
Charge. Adjust electrolyte level. Check aircraft voltage regulator. If OK, reduce maintenance interval. Complete failure to operate Defective connection in equipment circuitry in which battery is installed, such as broken lead, inoperative relay, or improper receptacle installation End terminal connector loose or disengaged Poor intercell connections Open circuit or dry cell Check and correct external circuitry. Clean and retighten hardware using proper torque values. Replace defective cell. Excessive spewage of electrolyte High charge voltage High temperature during charge Electrolyte level too high Loose or damaged vent cap Damaged cell and seal Clean battery, charge, and adjust electrolyte level.
Clean battery, tighten or replace cap, charge, and adjust electrolyte level. Short out all cells to 0 volts, clean battery, replace defective cell, charge, and adjust electrolyte level. 9-26 discharge side of the battery venting system. • Installing batteries—When installing batteries in an aircraft, exercise care to prevent inadvertent shorting of the battery terminals. Serious damage to the aircraft structure (frame, skin and other subsystems, avionics, wire, fuel, etc.) can be sustained by the resultant high discharge of electrical energy. This condition may normally be avoided by insulating the terminal posts during the installation process. Remove the grounding lead first for battery removal, then the positive lead.
Connect the grounding lead of the battery last to minimize the risk of shorting the hot terminal of the battery during installation. • Battery hold down devices—Ensure that the battery hold down devices are secure, but not so tight as to exert excessive pressure that may cause the battery to buckle causing internal shorting of the battery. • Quick-disconnect type battery—If a quick-disconnect type of battery connector that prohibits crossing the battery lead is not employed, ensure that the aircraft wiring is connected to the proper battery terminal. Reverse polarity in an electrical system can seriously damage a battery and other electrical components.
Ensure that the battery cable connections are tight to prevent arcing or a high resistance connection.
Troubleshooting
See Figure 9-39 for a troubleshooting chart. DC Generators & Controls DC generators transform mechanical energy into electrical energy. As the name implies, DC generators produce direct current and are typically found on light aircraft. In many cases, DC generators have been replaced with DC alternators. Both devices produce electrical energy to power the aircraft’s electrical loads and charge the aircraft’s battery. Even though they share the same purpose, the DC alternator and DC generator are very different. DC generators require a control circuit in order to ensure the generator maintains the correct voltage and current for the current electrical conditions of the aircraft. Typically, aircraft generators maintain a nominal output voltage of approximately 14 volts or 28 volts.
Generators The principles of electromagnetic induction were discussed earlier in this chapter. These principles show that voltage is induced in the armature of a generator throughout the entire 360° rotation of the conductor. The armature is the rotating portion of a DC generator. As shown, the voltage being induced is AC. [Figure 9-40] Since the conductor loop is constantly rotating, some means – Voltage + Voltage Maximum Minimum 0° Maximum 90° 270° 360° 1 cycle 180° N S B A stationary. must be provided to connect this loop of wire to the electrical loads. As shown in Figure 9-41, slip rings and brushes can be used to transfer the electrical energy from the rotating loop to the stationary aircraft loads. The slip rings are connected to the loop and rotate; the brushes are stationary and allow a current path to the electrical loads. The slip rings are typically a copper material and the brushes are a soft carbon substance.
It is important to remember that the voltage being produced by this basic generator is AC, and AC voltage is supplied to the slip rings. Since the goal is to supply DC loads, some means must be provided to change the AC voltage to a DC voltage. Generators use a modified slip ring arrangement, known as a commutator, to change the AC produced in the generator loop into a DC voltage. The action of the commutator allows the generator to produce a DC output. By replacing the slip rings of the basic AC generator with two half cylinders (the commutator), a basic DC generator is obtained. In Figure 9-42, the red side of the coil is connected to the red segment and the amber side of the coil to the amber segment. The segments are insulated from each other. The two stationary brushes are placed on opposite sides of the 9-27 Induced EMF 1 Revolution A EB C D commutator and are so mounted that each brush contacts each segment of the commutator as the commutator revolves simultaneously with the loop. The rotating parts of a DC generator (coil and commutator) are called an armature.
As seen in the very simple generator of Figure 9-42, as the loop rotates the brushes make contact with different segments of the commutator. In positions A, C, and E, the brushes touch the insulation between the brushes; when the loop is in these positions, no voltage is being produced. In position B, the positive brush touches the red side of the conductor loop. In position D, the positive brush touches the amber side of the armature conductor. This type of connection reversal changes the AC produced in the conductor coil into DC to power the aircraft. An actual DC generator is more complex, having several loops of wire and commutator segments.
Because of this switching of commutator elements, the red brush is always in contact with the coil side moving downward, and the amber brush is always in contact with the coil side moving upward. Though the current actually reverses its direction in the loop in exactly the same way as in the AC generator, commutator action causes the current to flow always in the same direction through the external circuit or meter. The voltage generated by the basic DC generator in for each revolution of the loop. This variation of DC voltage is called ripple and may be reduced by using more loops, or coils, as shown in Figure 9-43.
As the number of loops is increased, the variation between maximum and minimum values of voltage is reduced [Figure 9-43], and the output voltage of the generator approaches a steady DC value. For each additional loop in the rotor, another two commutator segments is required. A photo of a typical DC generator commutator is shown in Construction Features of DC Generators The major parts, or assemblies, of a DC generator are a field frame, a rotating armature, and a brush assembly. The parts of a typical aircraft generator are shown in Figure 9-45. Field Frame The frame has two functions: to hold the windings needed to produce a magnetic field, and to act as a mechanical support for the other parts of the generator. The actual electromagnet A B C D E 0 1/4 1/2 3/4 1 Induced EMF Revolutions (B) S N the voltage.
9-28 conductor is wrapped around pieces of laminated metal called field poles. The poles are typically bolted to the inside of the frame and laminated to reduce eddy current losses and serve the same purpose as the iron core of an electromagnet; they concentrate the lines of force produced by the field coils. The field coils are made up of many turns of insulated wire and are usually wound on a form that fits over the iron core of the pole to which it is securely fastened. [Figure 9-46] A DC current is fed to the field coils to produce an electromagnetic field. This current is typically obtained from an external source that provides voltage and current Air scoop Brush connector bars Commutator Steel ring Commutator end frame regulation for the generator system. Generator control systems are discussed later in this chapter.
Armature The armature assembly of a generator consists of two primary elements: the wire coils (called windings) wound around an iron core and the commutator assembly. The armature windings are evenly spaced around the armature and mounted on a steel shaft. The armature rotates inside the magnetic field produced by the field coils. The core of the armature acts as an iron conductor in the magnetic field and, for this reason, is laminated to prevent the circulation of eddy currents. A typical armature assembly is shown in Figure 9-47. Commutators commutator. The commutator is located at the end of an armature and consists of copper segments divided by a thin insulator. The insulator is often made from the mineral mica.
The brushes ride on the surface of the commutator forming the electrical contact between the armature coils and the external circuit. A flexible, braided copper conductor, commonly called a pigtail, connects each brush to the external circuit. The brushes are free to slide up and down in their holders in order to follow any irregularities in the surface of the commutator. The constant making and breaking of electrical connections between the brushes and the commutator segments, along with Connector lugs Sealed ball bearings Field frame Drive end frame Drive shaft Brush and holder Pole shoe Screw Field winding Field frame Armature Drive end 9-29 Commutator Coils Shaft the friction between the commutator and the brush, causes brushes to wear out and need regular attention or replacement.
For these reasons, the material commonly used for brushes is high-grade carbon. The carbon must be soft enough to prevent undue wear of the commutator and yet hard enough to provide reasonable brush life. Since the contact resistance of carbon is fairly high, the brush must be quite large to provide a current path for the armature windings. The commutator surface is highly polished to reduce friction as much as possible. Oil or grease must never be used on a commutator, and extreme care must be used when cleaning it to avoid marring or scratching the surface.
Types of DC Generators
There are three types of DC generators: series wound, parallel (shunt) wound, and series-parallel (or compound wound). The appropriate generator is determined by the connections to the armature and field circuits with respect to the external circuit. The external circuit is the electrical load powered by the generator. In general, the external circuit is used for charging the aircraft battery and supplying power to all electrical equipment being used by the aircraft. As their names imply, windings in series have characteristics different from windings in parallel. Mica V-ring Front V-ring Commutator bar Mica Iron shell Back V-ring with mica inner and outer rings for insulationSlots Tightening nut Iron ring Commutator bars Mica insulation between bars 9-30
Series Wound DC Generators
The series generator contains a field winding connected in series with the external circuit. [Figure 9-49] Series generators have very poor voltage regulation under changing load, since the greater the current is through the field coils to the external circuit, the greater the induced EMFs and the greater the output voltage is. When the aircraft electrical load is increased, the voltage increases; when the load is decreased, the voltage decreases. Since the series wound generator has such poor voltage and current regulation, it is never employed as an airplane generator. Generators in airplanes have field windings, that are connected either in shunt or in compound formats.
Parallel (Shunt) Wound DC Generators
A generator having a field winding connected in parallel with the external circuit is called a shunt generator. [Figure 9-50] It should be noted that, in electrical terms, shunt means parallel. Therefore, this type of generator could be called either a shunt generator or a parallel generator. In a shunt generator, any increase in load causes a decrease in the output voltage, and any decrease in load causes an increase output voltage. This occurs since the field winding is connected in parallel to the load and armature, and all the current flowing in the external circuit passes only through the armature winding (not the field).
As shown in Figure 9-50A, the output voltage of a shunt generator can be controlled by means of a rheostat inserted in series with the field windings. As the resistance of the field circuit is increased, the field current is reduced; consequently, the generated voltage is also reduced. As the field resistance NS + − Field rheostat Field winding Load A B NS + − Field rheostat Field winding Load Shunt circuit Main circuit Armature winding ArmatureField coils is decreased, the field current increases and the generator output increases. In the actual aircraft, the field rheostat would be replaced with an automatic control device, such as a voltage regulator.
Compound Wound DC Generators
A compound wound generator employs two field windings one in series and another in parallel with the load. [Figure 9-51] This arrangement takes advantage of both the series and parallel characteristics described earlier. The output of a compound wound generator is relatively constant, even with changes in the load.
Generator Ratings
A DC generator is typically rated for its voltage and power output. Each generator is designed to operate at a specified voltage, approximately 14 or 28 volts. It should be noted that aircraft electrical systems are designed to operate at one of these two voltage values. The aircraft’s voltage depends on which battery is selected for that aircraft. Batteries are either 12 or 24 volts when fully charged. The generator selected must have a voltage output slightly higher than the battery voltage. Hence, the 14- or 28-volt rating is required for aircraft DC generators. 9-31 A B NS + − Series field winding Parallel field winding Load Armature winding Series field coil To load Armature Shunt field coil Compound wound The power output of any generator is given as the maximum number of amperes the generator can safely supply. Generator rating and performance data are stamped on the nameplate attached to the generator. When replacing a generator, it is important to choose one of the proper ratings.
The rotation of generators is termed either clockwise or counterclockwise, as viewed from the driven end. The direction of rotation may also be stamped on the data plate. It is important that a generator with the correct rotation be used; otherwise, the polarity of the output voltage is reversed. The speed of an aircraft engine varies from idle rpm to takeoff rpm; however, during the major portion of a flight, it is at a constant cruising speed. The generator drive is usually geared to turn the generator between 1 1⁄8 and 11⁄2 times the engine crankshaft speed. Most aircraft generators have a speed at which they begin to produce their normal voltage. Called the “coming in” speed, it is usually about 1,500 rpm.
DC Generator Maintenance
The following information about the inspection and maintenance of DC generator systems is general in nature because of the large number of differing aircraft generator systems. These procedures are for familiarization only. Always follow the applicable manufacturer’s instructions for a given generator system. In general, the inspection of the generator installed in the aircraft should include the following items: 1. Security of generator mounting. 2. Condition of electrical connections. 3. Dirt and oil in the generator. If oil is present, check engine oil seals. Blow out any dirt with compressed air.
4. Condition of generator brushes. 5. Generator operation. 6. V oltage regulator operation. Sparking of brushes quickly reduces the effective brush area in contact with the commutator bars. The degree of such sparking should be determined. Excessive wear warrants a detailed inspection and possible replacement of various components. [Figure 9-52] Manufacturers usually recommend the following procedures to seat brushes that do not make good contact with slip rings or commutators. Lift the brush sufficiently to permit the insertion of a strip of extra-fine 000 (triple aught) grit, or finer, sandpaper under the brush, rough side towards the carbon brush. [Figure 9-53] Pull the sandpaper in the direction of armature rotation, being careful to keep the ends of the sandpaper as close to the slip ring or commutator surface as possible in order to avoid rounding the edges of the brush. When pulling the sandpaper back to the starting point, raise the brush so it does not ride on the sandpaper. Sand the brush only in the direction of rotation. Carbon dust resulting from brush sanding should be thoroughly cleaned from all parts of the generators after a sanding operation.
After the generator has run for a short period, brushes should be inspected to make sure that pieces of sand have not become 9-32 Unseated brush 000 sandpaper (sand side next to brush) Properly seated brush 1/32" to 1/16" embedded in the brush. Under no circumstances should emery cloth or similar abrasives be used for seating brushes (or smoothing commutators), since they contain conductive materials that cause arcing between brushes and commutator bars. It is important that the brush spring pressure be correct. Excessive pressure causes rapid wear of brushes. Too little pressure, however, allows bouncing of the brushes, resulting in burned and pitted surfaces. The pressure recommended by the manufacturer should be checked by the use of a spring scale graduated in ounces. Brush spring tension on some generators can be adjusted. A spring scale is used to measure the pressure that a brush exerts on the commutator.
Flexible low-resistance pigtails are provided on most heavy current carrying brushes, and their connections should be securely made and checked at frequent intervals. The pigtails should never be permitted to alter or restrict the free motion of the brush. The purpose of the pigtail is to conduct the current from the armature, through the brushes, to the external circuit of the generator. Generator Controls Theory of Generator Control All aircraft are designed to operate within a specific voltage range (for example 13.5–14.5 volts). And since aircraft operate at a variety of engine speeds (remember, the engine drives the generator) and with a variety of electrical demands, all generators must be regulated by some control system. The generator control system is designed to keep the generator output within limits for all flight variables. Generator control systems are often referred to as voltage regulators or generator control units (GCU).
Aircraft generator output can easily be adjusted through control of the generator’s magnetic field strength. Remember, the strength of the magnetic field has a direct effect on generator output. More field current means more generator output and vice versa. Figure 9-54 shows a simple generator control used to adjust field current. When field current is controlled, generator output is controlled. Keep in mind, this system is manually adjusted and would not be suitable for aircraft. Aircraft systems must be automatic and are therefore a bit more complex. There are two basic types of generator controls: electromechanical and solid-state (transistorized). The electromechanical type controls are found on older aircraft and tend to require regular inspection and maintenance. Solid- state systems are more modern and typically considered to have better reliability and more accurate generator output control.
Functions of Generator Control Systems Most generator control systems perform a number of functions related to the regulation, sensing, and protection of the DC generation system. Light aircraft typically require a less complex generator control system than larger multiengine aircraft. Some of the functions listed below are not found on light aircraft. Voltage Regulation The most basic of the GCU functions is that of voltage regulation. Regulation of any kind requires the regulation unit to take a sample of a generator output and compare that sample to a known reference. If the generator’s output Generator control Load Shunt field+ − B 9-33 voltage falls outside of the set limits, then the regulation unit must provide an adjustment to the generator field current.
Adjusting field current controls generator output. Overvoltage Protection The overvoltage protection system compares the sampled voltage to a reference voltage. The overvoltage protection circuit is used to open the relay that controls the field excitation current. It is typically found on more complex generator control systems. Parallel Generator Operations On multiengine aircraft, a paralleling feature must be employed to ensure all generators operate within limits. In general, paralleling systems compare the voltages between two or more generators and adjust the voltage regulation circuit accordingly.
Overexcitation Protection When one generator in a paralleled system fails, one of the generators can become overexcited and tends to carry more than its share of the load, if not all of the loads. Basically, this condition causes the generator to produce too much current. If this condition is sensed, the overexcited generator must be brought back within limits, or damage occurs. The overexcitation circuit often works in conjunction with the overvoltage circuit to control the generator. Differential Voltage This function of a control system is designed to ensure all generator voltage values are within a close tolerance before being connected to the load bus. If the output is not within the specified tolerance, then the generator contactor is not allowed to connect the generator to the load bus.
Reverse Current Sensing If the generator cannot maintain the required voltage level, it eventually begins to draw current instead of providing it. This situation occurs, for example, if a generator fails. When a generator fails, it becomes a load to the other operating generators or the battery. The defective generator must be removed from the bus. The reverse current sensing function monitors the system for a reverse current. Reverse current indicates that current is flowing to the generator not from the generator. If this occurs, the system opens the generator relay and disconnects the generator from the bus.
Generator Controls for High-Output Generators Most modern high-output generators are found on turbine- powered corporate-type aircraft. These small business jets and turboprop aircraft employ a generator and starter combined into one unit. This unit is referred to as a starter- generator. A starter-generator has the advantage of combining two units into one housing, saving space and weight. Since the starter-generator performs two tasks, engine starting and generation of electrical power, the control system for this unit is relatively complex. A simple explanation of a starter-generator shows that the unit contains two sets of field windings. One field is used to start the engine and one used for the generation of electrical power. [Figure 9-55] During the start function, the GCU must energize the series field and the armature causes the unit to act like a motor.
During the generating mode, the GCU must disconnect the series field, energize the parallel field, and control the current produced by the armature. At this time, the starter- generator acts like a typical generator. Of course, the GCU must perform all the functions described earlier to control voltage and protect the system. These functions include voltage regulation, reverse current sensing, differential voltage, overexcitation protection, overvoltage protection, and parallel generator operations. A typical GCU is shown in Figure 9-56. In general, modern GCUs for high-output generators employ solid-state electronic circuits to sense the operations of the generator or starter-generator. The circuitry then controls a series of relays and/or solenoids to connect and disconnect the unit to various distribution buses. One unit found in almost all voltage regulation circuitry is the zener diode. The zener diode is a voltage sensitive device that is used to monitor system voltage. The zener diode, connected in conjunction to the GCU circuitry, then controls the field current, which in turn controls the generator output.
Generator Controls for Low-Output Generators A typical generator control circuit for low-output generators modifies current flow to the generator field to control LOAD Armature Series field Parallel (shunt) field 9-34 generator output power. As flight variables and electrical loads change, the GCU must monitor the electrical system and make the appropriate adjustments to ensure proper system voltage and current. The typical generator control is referred to as a voltage regulator or a GCU. Since most low-output generators are found on older aircraft, the control systems for these systems are electromechanical devices. (Solid-state units are found on more modern aircraft that employ DC alternators and not DC generators.) The two most common types of voltage regulator are the carbon pile regulator and the three-unit regulator. Each of these units controls field current using a type of variable resistor.
Controlling field current then controls generator output. A simplified generator control circuit is shown in Figure 9-57. Carbon Pile Regulators The carbon pile regulator controls DC generator output by sending the field current through a stack of carbon discs (the carbon pile). The carbon discs are in series with the generator field. If the resistance of the discs increases, the field current decreases and the generator output goes down. If the resistance of the discs decreases, the field current increases and generator output goes up. As seen in Figure 9-58, a voltage coil is installed in parallel with the generator output leads. The voltage coil acts like an electromagnet that increases or decrease strength as generator output voltage changes. The magnetism of the voltage coil controls the pressure on the carbon stack. The pressure on the carbon stack controls the resistance of the carbon; the resistance of the carbon controls field current and the field current controls generator output.
Carbon pile regulators require regular maintenance to ensure accurate voltage regulation; therefore, most have been replaced on aircraft with more modern systems. Three-Unit Regulators The three-unit regulator used with DC generator systems is made of three distinct units. Each of these units performs a specific function vital to correct electrical system operation. A typical three-unit regulator consists of three relays mounted in a single housing. Each of the three relays monitors generator outputs and opens or closes the relay contact points according to system needs. A typical three- unit regulator is shown in Figure 9-59.
Voltage Regulator The voltage regulator section of the three-unit regulator is used to control generator output voltage. The voltage Armature Generator controlField circuit Generator output to electrical loads Field winding Armature Carbon stack Field Voltage coil 9-35 regulate voltage, limit current, and prevent reverse current flow. DC generator Voltage regulator Armature Resistance To electrical loads Contact points Voltage coil Field currentField circuit regulator monitors generator output and controls the generator field current as needed. If the regulator senses that system voltage is too high, the relay points open and the current in the field circuit must travel through a resistor. This resistor lowers field current and therefore lowers generator output. Remember, generator output goes down whenever generator field current goes down.
As seen in Figure 9-60, the voltage coil is connected in parallel with the generator output, and it therefore measures the voltage of the system. If voltage gets beyond a predetermined limit, the voltage coil becomes a strong magnet and opens the contact points. If the contact points are open, field current must travel through a resistor and therefore field current goes down. The dotted arrow shows the current flow through the voltage regulator when the relay points are open. Since this voltage regulator has only two positions (points open and points closed), the unit must constantly be in adjustment to maintain accurate voltage control. During normal system operation, the points are opening and closing at regular intervals. The points are in effect vibrating. This type of regulator is sometimes referred to as a vibrating- type regulator. As the points vibrate, the field current raises and lowers and the field magnetism averages to a level that maintains the correct generator output voltage. If the system requires more generator output, the points remain closed longer and vice versa.
Current Limiter The current limiter section of the three-unit regulator is designed to limit generator output current. This unit contains a relay with a coil wired in series with respect to the generator output. As seen in Figure 9-61, all the generator output current must travel through the current coil of the relay. This creates a relay that is sensitive to the current output of the generator. That is, if generator output current increases, the relay points open and vice versa. The dotted line shows the current flow to the generator field when the current limiter points are open. It should be noted that, unlike the voltage regulator relay, the current limiter is typically closed during normal flight. Only during extreme current loads must the current limiter points open; at that time, field current is lowered and generator output is kept within limits.
Reverse-Current Relay The third unit of a three-unit regulator is used to prevent current from leaving the battery and feeding the generator. This type of current flow would discharge the battery and is opposite of normal operation. It can be thought of as a reverse current situation and is known as reverse-current relay. The simple reverse-current relay shown in Figure 9-62 contains both a voltage coil and a current coil. The voltage coil is wired in parallel to the generator output and is energized any time the generator output reaches its DC generator Current limiter Armature To electrical loads Contact points (NC)Current coil Field circuit 9-36